    Functions
    Check synchronising
    The relay checks that the two part of the
    system are in synchronism by measuring
    the angle and the slip frequency
    between the line voltage and the bus
    voltage. Auto-reclose is blocked if these
    values exceed the phase angle and slip
    frequency settings. Manual closure is
    blocked if these values exceed the system
    angle and system slip settings.
    Selectable undervoltage and differential
    voltage measurements are available to
    block closure if the line and bus voltages
    are not compatible.
    To allow the circuit breaker to be closed
    onto an uncharged line, live line/ dead
    bus, dead line/ dead bus and dead
    line/ live bus detectors are included.
    These allow reclosure when the voltage
    on the line and/ or the bus VT is below a
    preset value.