Mini Server Environment Monitoring System
Specification
PT. GLOBAL MEGA VISION as an Indonesian Main Distibutor of Mini Server Environment Monitoring System and various type of sensors.
Features & Applications:
The Mini Server Environment Monitoring System monitors critical environmental conditions ( such as temperature, humidity, and water leakage) that could destroy network components in your server room. When a sensor goes out of range of a configurable threshold, the system will notify you via email, SNMP traps, web-page alerts, a visual indicator ( red LED) , and SMS messages ( via external GSM or 3G modem) .
* Monitor and manage server room environmental conditions over IP.
* Sensors supported:
- 2 temperature/ humidity sensors
- 1 liquid detection sensor
- 4 digital inputs sensitive to contact closure
* Alerts are posted in message log, which is accessible through Web user interface.
- The log can be downloaded as a tab-delimited plain text file
* Integrates with various Open Source monitoring packages — Nagios and MRTG.
* Flexible Zero-RU mounting.
- Mounting tabs included.
- Optional DIN mounting available.
* Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
* Optional industrial mini server environment monitoring system for high temperature environments. This industrial system has the ability to operate and monitor in harsh environments at high temperatures up to 167° F ( 75° C) .
Specifications:
Temperature/ Humidity Inputs
* Two female RJ45 connectors for connecting temperature sensors, humidity sensors and/ or combined temperature/ humidity sensors.
Water Detection Cable Input
* One screw terminal pair for connecting liquid detection sensor.
o Additional water detection sensors can be connected to the dry contact closures.
* Output voltage: + 5V DC.
* Current limited to 10mA
* Maximum resistance to close contact: 300K Ohm
Dry Contact Closures
* Four screw terminal pairs for connecting dry contact devices.
* Potential-free.
* Output voltage: + 5 V DC
* Current limited to 10 mA
* Maximum resistance to close contact: 300K Ohm
Ethernet Port
* One female RJ45 connector with LEDs.
* 10 BaseT Ethernet interface.
RS232 Port
* One female RJ45 connector for controlling a GSM modem.
* Supports 3-wire interface ( Tx, Rx and GND)
* Used for flash upgrades ( includes DB9F-RJ45F adapter) .
* GSM modem supported: Teltonika WirelessCom/ G10
* 3G modem supported: NetComm N3GS003
Protocols
* HTTP, SNMP V1, SMTP, TCP/ IP, UDP, DHCP, WAP 2.0
* Compatible with any SNMP management software.
* Operates and configures via an HTTP web page.
* An IP address can be assigned to the ENVIROMUX-MINI automatically by a DHCP server.
* Generates SNMP traps, email alerts, and syslog messages.
* Email alerts can be sent to three addresses.
* Up to four users can access the Web interface simultaneously.
* OIDs for sensor and contact values for ENVIROMUX-MINI.
Dimensions
* WxDxH ( in.) : 5.6x2x2
Environmental
* Operating temperature:
o ENVIROMUX-MINI: 32° F to 100° F ( 0° C to 38° C) .
o ENVIROMUX-MINI-IND: 32° F to 167° F ( 0° C to 75° C) .
* Storage temperature:
o ENVIROMUX-MINI: -20° F to 140° F ( -30° C to 60° C) .
o ENVIROMUX-MINI-IND: -20° F to 185° F ( -30° C to 85° C) .
* Operating and Storage Relative Humidity: 17 to 90% non-condensing RH.
Regulatory Approvals
* ENVIROMUX-MINI: CE, cUL, UL ( UL File # : E238791-A5-UL-1) , RoHS
* ENVIROMUX-MINI-IND: CE, cUL, UL ( UL File # : E238791-A5-UL-1) , RoHS
Power
* 110 or 220 VAC at 50 or 60 Hz via AC adapter.
* Power consumption: 5W
* Use the PWR-48V-5V1A DC-DC power converter to install the ENVIROMUX-MINI in a Telecom environment.
* Use the ENVIROMUX-POE Power over Ethernet Adapter to locate the ENVIROMUX Mini up to 300 feet away from a Power Over Ethernet switch.
MTBF
* 80, 327 hrs.