    ARMI-TC.09 ( Cooling Water Treatment Test Kit)

    Quantity Order:
    Origin:
    Indonesia

    Specification :

    INDICATION

    ARMI – TC.09 is for Alkalinity, Chloride and Iron testing.

    Function

    Alkalinity Test Kirt

    To determine the Alkalinity level

    * Take cooling process water about 5 ml, put in plastic tube.
    * Put in 1 ( one) drop of Bromophenol Blue Indicator, then stir it. If the solution color is yellow then Alkalinity = 0.
    * If the solution color is purple, continue with titration using HI 3811-0 ( Reagent : acid solution)
    * Take ( HI 3811-0) reagent using a syringe, until the syringe' s scale limit = 0.
    * Put in the solution until titration solution turns yellow.
    * Alkalinity result can be viewed from regent use inside the syringe, then the total use multiplied by a factor of 300, result is in units of mg/ l ( ppm)

    Chloride Test Kirt
    To determine the Chloride level

    * Take cooling process water about 5 ml, put in plastic tube.
    * Put in 2 ( two) drops of Diphenylcarbozone Indicator, then stir it. The solution color will be red violet.
    * While still stirring inside the plastic tube, put in Nitric Acid solution until the color of the solution is yelllow.
    * Take HI 3815-0 ( Mercuric Nitrate Solution) using a syringe, until the syringe' s scale limit = 0.
    * Put in the solution until titration solution turns yellow.
    * Put in the solution until titration solution turns violet.
    * Chloride result can be viewed from regent use inside the syringe, then the total use multiplied by a factor of 1000, result is in units of mg/ l ( ppm)

    Iron Test Kirt
    To determine the Iron level

    * Take 10 ml sample water, put in plastic tube.
    * Put in 1 sachet reagent Iron, then stir.
    * Wait for about 6 minutes, put color comparator into the solution inside the tube.
    * Compare sample solution with color comparator.
    * Iron result can be read from color comparator, result is in units of mg/ l ( ppm)

    Standard for Cooling Water Process

    * PH : 9
    * Chloride : < 50 ppm
    * Alkalinity : 100 – 300 ppm
    * Iron : < 5 ppm

    Caution

    * Reagent only for testing.
    * Put away from children
    * Clean ( wash) hands after use.